| INPUT |
|
| VOLTAGE RANGE |
180 - 270 VAC for Single Phase, 360 - 460 for Three Phase |
| FREQUENCY |
46 TO 54 Hz |
| PHASE |
Single phase & 3 Phase 4 Wires |
| DC |
72V - 360V DC |
| OUTPUT |
|
| VOLTAGE |
230VAC / 415VAC + 2% |
| FREQUENCY |
50Hz + 1% |
| WAVEFORM |
Pure sine wave |
| HARMONIC DISTORTION (THD) |
<3% (for linear load) <5% (for non linear load) |
| LOADPOWER FACTOR |
0.7 Lagging |
| LOADCREST FACTOR |
4:1 |
| OVERLOAD |
105% Continuously and 200% for 2 sec. |
| AUDIBLE NOISE |
Less than 40db at 1 meter |
| OPERATING TEMP |
0oc to 50oC, Humidity-Max. 95% Non Condensing |
| BATTERY TYPE |
Sealed lead Acid Maintenance free Lead Acid tubular (Battery voltage AH and quantity depending on backup time) |
| CHARGER |
Solid state float cum boost charger with automatic boost/trickle charge modes with current Limiting features |
INDICATION & ALARMS MAINS ON INVERTER ON CHARGING ON OVERLOAD BATTERY LOW |
LED Indication LED Indication LED Indication LED Indication & Alarm LED Indication & Alarm |
| DIGITAL METERING |
NUMERIC LED for Input I/P, O/P and Battery Voltage |
| PROTECTION |
Advance electronic protection for device safety backed up with MCBs MCCBs/ fast action fuses. High speed pulse blanking, electronic over voltage/undervoltage Over Temperature |
| ISOLATION OF POWER |
|
| OUTPUT |
With isolation transformer at output |
| INPUT |
MCB / MCCB |
| BATTERY |
Fuse Link, HRC Fuse, MCB (Optional) |
| BYPASS |
Optional |